ASTM A53 Pipe,ASME SA53 Pipe

ASTM A53 Pipe,ASME SA53 Pipe
ASTM A53 Pipe,ASME SA53 Pipe
ASTM A53 Pipe,ASME SA53 Pipe
Steel pipe
ASTM A53 Standard specification covers Seamless and Welded, Black and Hot-Dipped Galvanized nominal (average) wall pipe for coiling, bending, flanging and other special purposes and is suitable for welding.
The steel for both seamless and welded pipe shall be made by one or more of the following processes: open-hearth, electric furnace, or basic-oxygen. The weld seam of electric-resistance welded pipe in Grade B shall be heat treated after welding.
A53 pipe comes in three types and two grades
  • A53 Type F, which is longitudinally furnace butt welded or continuous welded (Grade A only)
  • A53 Type E, which is longitudinally electric resistance welded (Grades A and B)
  • A53 Type S, which is seamless pipe, produced by hot working, and possibly cold finishing, the steel (Grades A and B). ASTM A53, Type S is now currently an outdated specification and has been replaced by ASTM A106 specification for seamless carbon steel pipe.
This is a standard set by the standards organization ASTM International, a voluntary standards development organizations that sets technical standards for materials, products, systems, and services.
This specification covers Seamless and Welded, Black and Hot-Dipped Galvanized nominal (average) wall pipe for coiling, bending, flanging and other special purposes and is suitable for welding. Continuous-Welded pipe is not intended for flanging. Purpose for which pipe is intended should be stated on order. It shall be permissible to furnish pipe having other dimensions provided that such pipe complies with all other requirements of this specification. Supplementary requirements of an optional nature are provided and shall apply only when specified by the purchaser.
Note 1. The dimensionless designators NPS (nominal pipe size) [DN (diameter nominal)] have been substituted in this specification for such traditional terms as ‘nominal diameter,’ ‘size,’ and ‘nominal size.’
Note 2. The term nominal wall thickness has been assigned for the purpose of convenient designation, existing in name only, and is used to distinguish it from the actual wall thickness, which may vary over or under the nominal wall thickness.

Permissible Variations in Wall Thickness

The minimum wall thickness at any point shall not be more than 12.5% under the nominal wall thickness specified.

Permissible Variations in Weights per Foot

Weight of any length shall not vary more than 10% over and 3.5% under that specified.
NOTE-NPS 4 and smaller-weighed in lots. Larger sizes shall be weighed separately by length.

Chemical Requirements ASTM A53

Chemical
elements
Type SType EType F
(SMLS)(ERW)(FW)
Gr. AGr.BGr. AGr. BGr. A
Carbon max. %0.250.30.250.30.3
Manganese %0.951.20.951.21.2
P, max. %0.050.050.050.050.05
Sulfur, max. %0.0450.0450.0450.0450.045
Copper, max.%0.40.40.40.40.4
Nickel, max. %0.40.40.40.40.4
Chromium, max. %0.40.40.40.40.4
Mo, max. %0.150.150.150.150.15
Vanadium, max. %0.080.080.080.080.08
The total composition for these five elements shall not exceed 1.00%.

Tensile Requirements

PropertiesSMLS & ERWCon. welded
Grade AGrade BGrade
Tensile Strength, min., psi48,00060,00045,000
Yield Strength, min., psi30,00035,00025,000
  • Seamless and Electric-Resistance-Welded — Bending, flattening, tensile on one length of pipe from each lot of 500 lengths or less of a size.
  • Continuous-Weld — Bending, flattening, tensile
  • Con. welded: Continuous-welded

General Information

Couplings — Applied handling tight. Couplings, 2″ and smaller straight tapped, other sizes taper tapped.
Thread Protection — Applied to pipe 4″ and larger.
End Finish (unless otherwise specified) –
STD or XS, or wall thicknesses less than 0.500 in. (excluding XXS): Plain and beveled
All XXS and wall thicknesses over 0.500 in.: Plain end square cut.

Hydrostatic testing

Hydrostatic inspection test pressures for plain end and threaded and coupled pipe are specified. Hydrostatic pressure shall be maintained for not less than 5 seconds for all sizes of seamless and electric-resistance-weld pipe.

Mechanical tests specified

  • Tensile Test — Transverse required on ERW for NPS 8 and large.
  • Sending Test (Cold) — STD and XS-NPS 2 and under XXS-NPS 1 1/4 and under.
ApplicationDegree of BendDiameter of Mandrel
For Normal A53 Uses9012 x nom dia. of pipe
For Close Coiling1808 x nom dia. of pipe
Flattening Test — NPS 2 and larger STD and XS. (Not required for XXS pipe.)

Get in Touch

Welcome to Sunny Steel Enterprise Ltd.

Sunny Steel provide a wide range of steel products as Steel pipes, Seamless tube and seamless pipes, Alloy pipes, Pipe fittings, Composite steel pipe used in the industry, construction etc.
You can get in touch by telephone, post, online or E-mail.
Please check the help section first to see if your question may be answered there.

Pipe fitting

Pipe fitting
Pipe fitting is work that involves the installation or repair of pipes or tubes. Pipes and tubes are necessary for a wide range of reasons.

Flanges General

Flanges General
A flange is a method of connecting pipes, valves, pumps and other equipment to form a piping system.

Seamless steel pipe >>

Seamless steel pipe >>
Seamless steel pipe is alos called CDS pipes (Cold drawn seamless pipe).